Features of -EVI Compressor 155KW Heat Pump COP 4.5 Eco Friendly cold climate -25 degrees Celsius
A split heat pump fresh air heat recovery system, comprising an outdoor unit and an indoor unit. The exhaust port of the compressor is connected to one port of the four-way valve after passing through the outdoor heat exchanger; the suction port of the compressor passes through all the ports. The gas-liquid separator is connected to the other port of the four-way valve; the other two ports of the four-way valve are respectively connected to the liquid pipe end of the first indoor heat exchanger and the second indoor heat exchanger through connecting pipes. The air pipe end of the heat exchanger; the housing of the indoor unit is provided with a partition to separate the inside of the housing into mutually isolated exhaust air ducts and fresh air ducts; the first indoor heat exchanger is arranged on the In the exhaust air duct; the second indoor heat exchanger is arranged in the fresh air duct; the first indoor heat exchanger and the second indoor heat exchanger are connected in series, and a throttling component is also arranged between them. The utility model can efficiently recover indoor exhaust energy, reduce energy waste, and can also reduce the noise of the compressor from being introduced into the room, thereby improving comfort
For further specification of Inverter 40HP 155 KW Split Heat Pump For Big Family Villa Use and other specifications, welcome to contact us!
Unit type | SJKRS-I60II /C | |
Specifications | 40HP | |
Power supply | Three-phase five-wire380V/50Hz | |
Heating mode | Direct heat/cycle type | |
Standard working condition | Heating capacity( kw ) | 155.1 |
Input Power(kW) | 34.5 | |
COP | 4.5 | |
Hot Water flow(m³/h) | 3.33 | |
High temperature condition | Heating capacity kw ) | 13.1.5 |
Input Power(kW) | 41.1 | |
COP | 3.2 | |
Hot Water flow(m³/h) | 1.51 | |
Low temperature condition | Heating capacity( kw ) | 94.5 |
Input Power(kW) | 33.8 | |
COP | 2.8 | |
Hot Water flow(m³/h) | 1.77 | |
Component Information | Size of water pipe joint | DN40 |
Water heat exchanger | Plate or sleeve heat exchanger | |
Air Heat Exchanger | Aluminum Fin for copper tube | |
compressor type | Semi-closed reciprocating | |
Operation Panel | Color touch screen | |
Maximum outlet temperature(℃) | 90℃ | |
Refrigerants | R744 (CO2 ) | |
Design pressure(MPa) | High side 15, low side 8 | |
Dimensions (length, width and height mm) | 2290x2270x1980 | |
Noise (dB) | 70 | |
Weight(kg) | 221360 | |
SCOPE of use | Feed water temperature(℃) | 5~ 40 |
Feed water pressure | 0.05~ 0.4 | |
Effluent temperature(℃) | 55~ 90 | |
Maximum flow | 6.5 | |
Ambient temperature(℃) | ’-20~43 |
Some projects for 40HP 155 KW Split Heat Pump For Big Family Villa Use
t3) low temperature working condition: ambient temperature DB-10 °C, using side initial water temperature 9 °C, termination water temperature 55 °c;2) high temperature effluent: Ambient Temperature DB 20 ° c/WB 15 ° C, using side initial water temperature 15 ° C, termination water temperature 90 ° c;
1) standard working conditions: ambient temperature DB 20 ° c/WB 15 ° C, using side initial water temperature 15 ° C, termination water temperature 55 ° c;
EVI Compressor 155KW Heat Pump COP 4.5 Eco Friendly cold climate -25 degrees Celsius